A screen in multiple languages is created; however, the displayed language does not change.
<Causes> A wrong language number is specified for the switch [Function: Language changeover]. (V8/TS series only) The screen is not refreshed after t... Show Detail
<Cause> When displaying a normal overlap or call-overlap part according to the status of the corresponding bit in read area "n + 1", this is recognize... Show Detail
The time and date is not displayed correctly.
The solutions vary depending on the screen data settings. Check the following settings. Setting location: V-SFT editor [System Setting]→[Unit Setting]→[SR... Show Detail
Pressing the reset switch does not clear history data.
<Causes> The switch is not pressed twice. The switch function is not set to [Reset]. The switch is disabled according to the interlock setting. ... Show Detail
MONITOUCH does not recognize the storage dvice.
<Causes> The file system of the storage device is not supported. The CF card cover is open (V8 series only). The error status is set in $s497 (or $s... Show Detail
Communication between the temperature controller and the V series is slow (V7 series).
To speed up communications, try the following method. The condition can also be improved as described below. <Baud rate> Increase the communicatio... Show Detail
Trend graphs cannot be displayed.
<Causes> No data is stored in the device memory address for each graph number. The number of points to display is not specified in the control device... Show Detail
The Card Format switch (SRAM format) is not effective when pressed.
<Causes> The set word count for [Memory Card Emulation Area] is too small. There is no memory card mode icon. <Solutions> Select [System ... Show Detail
The data displayed in a trend graph is different from the most recent data in the PLC.
<Cause> The trend graph is not redrawn. <Solution> The graph data once displayed is not updated unless the redraw command is specified. To ... Show Detail
The lamp lights up even though the bit in the lamp device memory is not ON.
<Cause> The lamp device memory is used redundantly. <Solution> Check if the same address as the lamp device memory is used in the screen dat... Show Detail