How to check the communication condition between the temperature controller and the V/TS
The temperature controller condition is output to the system device memory of the V/TS. Check the following addresses for each station number. [V8/TS] Sel... Show Detail
Pressing the touch switch activates nothing or activates a position that deviates from the switch.
Try performing touch switch testing and adjustment. <Method> Display the touch switch test screen. -V8/TS series Main Menu screen → [Main Menu] ... Show Detail
I want to connect to MICREX-SX but "Communication Error: Error Code received " occurs.
This is an address error. An invalid device memory is set in the screen program. The causes are listed below. Cause 1: X/Y device memory, P/PE link, or ... Show Detail
The PLC device memory address for a part is garbled as "??" or is "blank".
<Causes> When the PLC model setting is changed, it is replaced with device "??". PLC2 - 8 are set as "not used" (delete). Variable name cooperation ... Show Detail
<V-Server> Is the number of tags to be registered limited?
No. However, registering more tags will place a greater burden on V-Server and thus a polling time interval may become longer. Notes: It requires approx... Show Detail
Check the output device and set it correctly. For system device ($s/$T): It is not possible to write any value from remote screen to the monitored device. ... Show Detail
[Causes] WAV files or JPEG files are notstored in the correct folder. For WAV file replay, settings on a screen program is not correct. [Solutions] The loc... Show Detail
What are the types and sizes of protective sheet? (V8)
The types and sizes of protective sheet available with the TS/V8 series are listed below. MONITOUCH model Protective sheet type Size (mm) TS2060i... Show Detail
How to draw reference lines in a trend graph or trend sampling part
V-SFT Ver.6 [To draw four or less horizontal reference lines] Display the [Trend Graph] dialog and click [Contents]. Check a [Reference Line] to use and se... Show Detail
<Cause> The screen data you attempted to open includes a function not supported by the V-SFT version in use. <Solution> Update the V-SFT ver... Show Detail