I used only the MICREX-SX and electrical devices with CE Marking in a control panel. Can I show CE Marking on this control panel?
    
      I used only the MICREX-SX and electrical devices with CE Marking in a control panel. Can I show CE Marking on this control panel?
    
  
    - Category : 
 
    - 
      
    
 
  
 
    Answer
  
    No, you can't. The MICREX-SX shows an EC directive conformity declaration (self-declaration) as a single PLC unit. 
For the conformity declaration as control panel, you need to check the applicable standards for the control panel and
 consult with TUV or another appropriate certification authority before making a self-declaration.
[Related document]
For conformance with CE marking of control panel using Fuji Electric PLCs, refer to the user's manual 'Conformance
 with Standards (FEH249)'. 
In addition, for information on the applicable models, refer to the latest version of 'MICREX-SX Programmable
 Controllers MICREX-SX series SPH catalog (22B2-E-0004).