The variables I specified as retained by using D300win are not retained through a power failure. What can I do to solve the problem?
If battery-less operation is enabled under the 'CPU running definition' setting, the content of the retain memory is not retained. Disable battery-less opera...
Show Detail
- No:1350
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:36
-
With D300win V2, I created global variables first and edited a ladder but some variables do not appear on the pull-down list for variable name inpu...
One likely cause is that any of the following characters is used in the variable worksheet
(1) A double-byte space is used. Use a single-byte space or tab...
Show Detail
- No:1356
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:38
-
I compiled a project of the SPH Series and came across a memory shortage error. Is there any way to deal with this problem?
With the SPH Series, the memory boundaries between the non-retain, retain, system FB and user FB memory areas can be changed to change the size of the respec...
Show Detail
- No:1359
- Displayed Date:2023/04/25 19:00
-
With a project created by using D300win, is it possible to change the current value of the timer? If so, how can I change the value?
The current value of the timer can be changed.
Note, however, that a circuit for changing the current value of the timer must be added.
Show Detail
- No:1375
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:44
-
With D300win V2, I cannot monitor some of the variables in the global variable worksheet.
They cannot be monitored if the number of rows in the variable worksheet exceeds 2520.
Divide the variable worksheet so that the number of rows is 2500 or...
Show Detail
- No:1384
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 16:16
-
When I use D300win to add variables to a certain POU and compile it for comparison, a 'comparison error' occurs even in a POU irrelevant to the cha...
This is because when a compilation process is carried out, automatically assigned variables (variables for which AT specification is not used) and FB instanc...
Show Detail
- No:1336
- Displayed Date:2023/04/25 19:00
-
When compiling a D300win project, an error message appears saying 'This variable address: %M* 3.z is treated as a retain memory.' Why does this mes...
When you do not check 'RETAIN' on the variable worksheet (default), the variable is treated as a non-retain memory.
When you check 'RETAIN,' the variable i...
Show Detail
- No:1368
- Displayed Date:2023/04/25 19:00
-
Regarding description in the ST language, is it possible to write an expression such as 'variable name + 1' in the brackets of an array?
A description in the brackets of an array must only include values or variable names. Writing an expression in brackets is not possible.
Show Detail
- No:1307
- Displayed Date:2023/04/25 19:00
-
When I unzip a project in Expert (D300win), a message appears saying 'Pagelayout 'DEFAULT.PLT' already exists! Overwrite?' When does this message a...
The message appears when a zip project file (.zwt) contains 'DEFAULT.PLT' in which the page layout for project printing is set, and the page layout setting o...
Show Detail
- No:1472
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/09 13:30
-
Does the D300win offer any method to specify variable names (or direct addresses) indirectly on a program (like a specification method generally ca...
Index modification is not available with D300win.
This is because D300win is dedicated to programmable controllers (PLCs) conforming to the internal standar...
Show Detail
- No:1591