I creat user FB in StandardV3, and defined input/output parameter as word (WV). Can I directly access any bit within this parameter WV?
No, you cannot access the input (output) parameter (WV*, DV*) for which the data length is set in words/
double-words by using a bit address within the user ...
Show Detail
- No:1677
- Displayed Date:2023/04/25 19:00
-
When I defined array (example WL990[WL0]) as start addoress of FMOVE in StandardV2 loader, error was detected by error check. Why?
For the Standard loader V2, you cannot specify array data for the operand that specifies the first address. (An error is detected during the program check.) ...
Show Detail
- No:1665
- Displayed Date:2023/04/25 19:00
-
I converted a MICREX-F program to a MICREX-SX using StandardV3 loader. Contact and coil M8720 (TEMP0) which did not exist before conversion were cr...
The execution order of the contacts and coils in a ladder circuit partly differs between MICREX-F and
MICREX-SX. Therefore, if a MICREX-F program is convert...
Show Detail
- No:1657
- Displayed Date:2023/04/25 19:00
-
When comparing the project in CPU with that in the personal computer by Standard loader, a mismatch between the programs was detected. How can I fi...
You can display the mismatch circuit in the program and differences using the 'Verify' command of the Standard
loader.
After uploading the project from the...
Show Detail
- No:1664
- Displayed Date:2023/04/25 19:00
-
How can I enter tags (device comments) in a batch on Standard loader V3?
1) Double-click the 'Device' icon in the project view to open the device window.
2) Click the [Device Type] selection button (▼) and select a device for w...
Show Detail
- No:1527
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/09 13:45
-
I am creating a program using SX-Programmer Standard. How can I check the address range of the memory devices that can be used in a program?
You can check the address range of the CPU by using the loader or in the user's manual.
In the Standard loader, after creating a project, you can check the ...
Show Detail
- No:1480
- Displayed Date:2023/04/25 19:00
-
When I tried to download a project to the CPU with StandardV3, an error message appeared saying 'The size of Zip file exceeds the capacity.' and th...
The zip file size exceeds the capacity of the CPU. Zip files contain text files such as 'tags,' 'line comments,'
'texts in system definition' created during...
Show Detail
- No:1659
- Displayed Date:2023/04/25 19:00
-
When a double-word address is used with the Standard Loader (Type_ NP4H-SWN), how are words arranged in terms of the higher and lower order?
Data with an address with the smaller number is arranged on the lower-order side.
For example, DM0 consists of two words_ WM0 and WM1. WM0 is arranged on th...
Show Detail
- No:1305
- Displayed Date:2023/04/25 19:00
-
Of the communication port settings (MICREX-SX) of the Standard Loader (Type_ NP4H-SWN), the 'Use USB port' check box cannot be selected.
To make the 'Use USB port' check box selectable, the USB driver for MICREX-SX must be installed on the PC in use.
Install the USB driver (dedicated) conta...
Show Detail
- No:1306
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 14:31
-
Is it possible to use the SX control utility of D300win to back up a program written by using the Standard Loader (Type_ NP4H-SWN)?
Yes, it is possible.
Show Detail
- No:1393
- Displayed Date:2023/04/25 19:00