After I replaced an Ethernet module (Type_NP1L-ET1/ET2), it cannot communicate with the target device. What is a possible cause?
After I replaced an Ethernet module (Type_NP1L-ET1/ET2), it cannot communicate with the target device. What is a possible cause?
- Category :
-
Answer
The IP address and port standard No. of the self station of the Ethernet module are stored in the internal ROM of the Ethernet module. After replacing an Ethernet module, open the original program, check 'Module driver' on the window on which a program is loaded to the PLC, and then transfer the program.