I mounted the power supply module (Type_ NP1S-22) on the base board (Type_ NP1BS-06). The connector at the far left of the base board is not used. Does it cause any problem?

I mounted the power supply module (Type_ NP1S-22) on the base board (Type_ NP1BS-06). The connector at the far left of the base board is not used. Does it cause any problem?
Category : 

Answer

No, it doesn't.
A power supply module may occupy two slots (Type_ NP1S-22, NP1S-42) or one slot (Type_ NP1S-81, NP1S-91).
The connector at the far left of the base board is intended for a one-slot power supply module.