The feedback pulses of the pulse train duplex positioning control module (Type_ NP1F-MP2) have A and B phases only and do not have Z-phase pulses. Can I input pulse signals to detect a position?

The feedback pulses of the pulse train duplex positioning control module (Type_ NP1F-MP2) have A and B phases only and do not have Z-phase pulses. Can I input pulse signals to detect a position?
Category : 

Answer

The module counts feedback pulses even without Z-phase pulse signals. Note that when Z-phase pulse signals are not provided, origin return operation is disabled. (There will be no problem with manual operation.)