Is there a limit on the wiring length of P-link/PE-link cables?

Fuji Electric Global

Global
  • Font Size
  • S
  • M
  • L
  • No : 1281
  • Displayed Date : 2023/04/25 19:00
  • Updated DTM : 2023/06/09 13:09
  • Print

Is there a limit on the wiring length of P-link/PE-link cables?

Is there a limit on the wiring length of P-link/PE-link cables?
Category : 

Answer

Yes, both P-link and PE-link cables have limits on the wiring length.

[P-link]
・Electrical transmission line
 Total length of electrical transmission line: 250m
 Min. length between stations: 1m
・Optical transmission line
    Max. length between stations: 3km (GI type)
    In cascade connection: Max. 16 optical converters (FNC360A-C20) can be connected.

[PE-link]
・Electrical transmission line
 Total length of electrical transmission line: 500m
 Min. length between stations: 1m
・Optical transmission line
 Max. length between stations: 3km (GI type)
 In cascade connection: Max. 64 optical converters (FNC360A-C20) can be connected.

* For the specifications of the optical converter (FNC360A-C20),
   refer to the user's manual 'P/PE-link Optical Converter (FEH584).'