"Screen No. Error"
Check the value of "n+2" in [Read Area] and change it to the value of an existing screen number.
If the device memory of [Read Area] is unknown, check the following locations.
V8/TS series
Check position: V-SFT-6 editor [System Setting] →[Hardware Setting]→ [Read/Write Area]→ [Read Area]

Example) In the above screenshot, since the value of "n+2" in [Read Area] is "D00002", check the value of "D00002" on the PLC and change it to the value of an existing screen number if necessary.
* If the [GD-80 Compatible Read/Write Area] checkbox is selected in the
[GD-80 Compatible] tab window, check the lower 8 bits of the device memory
for "n+1" in [Read Area].
V7 series
Check position: V-SFT-5 editor [System Setting] →[PLC Communication] →[Communication Parameter] →[Main 1]

Example) In the above screenshot, since the value of "n+2" in [Read Area] is "D00002", check the value of "D00002" on the PLC and change it to the value of an existing screen number if necessary.
* If the [GD-80 Compatible Read/Write Area] checkbox is selected, check the
lower 8 bits of the device memory for "n+1" in [Read Area].
Double-click the value of "n+2" in [Read Area] displayed in the [System] window of the simulator and change it to the value of an existing screen number.