I want to show a multi-overlap using PLC command but the overlap does not appear.
I want to show a multi-overlap using PLC command but the overlap does not appear.
Category :
GLOBAL
>
HMI
>
V10/V9 series
>
Operation Troubles
Answer
Check the following points:
Multi-overlap (icon)
is not place on the screen.
Multi-overlap setting (icon) is not correct.
Macro commands are not correct.
To show multi-overlap using a switch, please click
here
.
To show multi-overlap using PLC command, please click
here
.
Go to [Home] or [Parts] > [Multi-overlap] and place a multi-overlap icon.
This icon still works when you place it outside editing area of the screen.
Double-click the multi-overlap icon and sselect [Multi] from [Overlap Setting] and select [Control Device] from [Display Method] pulldown box.
E.g.) Multi-overlap icon is set as below:
Control device: M0
Device for Overlap Library No. to Display: D101
To show the overlap library No. 3:
1) Enter "3" to D101 (Device for Overlap Library No. to Display).
2) Set the control device M0 to ON.