- No : 1594
- Displayed Date : 2023/04/25 19:00
-
Print
The system using a servo directly connected to the SX bus does not start. I confirmed that the system configuration definition is correct.
The system using a servo directly connected to the SX bus does not start. I confirmed that the system configuration definition is correct.
- Category :
-
Answer
When station number '0' is set on the servo, the station number set on the loader becomes effective.
If, however, you want to use the servo for fail-soft startup, you need to set its station number to a number other than '0' and set the same number on the loader.