<TELLUS-Remote> Are macro commands on the TELLUS remote screens executed?

  • Font Size
  • S
  • M
  • L
  • No : 4824
  • Displayed Date : 2025/12/01 13:53
  • Print

<TELLUS-Remote> Are macro commands on the TELLUS remote screens executed?

<TELLUS-Remote> Are macro commands on the TELLUS remote screens executed?

Category : 

Answer

 

In remote mode, only switch ON/OFF macro commands are executed.
Other macro commands than those switch macros are not executable.

 

Notes:
  • Neither SYS commands or indirect address are executed even they are coded in the switch ON/OFF macro commands. 
  • To use internal memory device in the switch macro commands, [Remote Monitor Setting] in the V-Server is required.

     
Procedure
  1. On V-Server, select the monitored device which you are going to execute switch macro commands on.
  2. Go to [Edit] > [Remote Monitor Setting].

     
  3. Click [Detail] buttton.  [Remote Operation in Macro] option appears.
    This options is valid when internal memory devices are used in the macro commands.
    Tick appropriate box(es) as necessary.

 

  • Read Internal Memory
    Values stored in the internal memory devices in the monitored device are read to execute macro commands. 

     
  • Write Internal Memory
    Execution results of the macro commands are stored in the internal memory devices in the monitored device.