How to check the operation of screens without connecting to a PLC
Connection between PC and MONITOUCH
[Step]


The [Simulator] window opens.
Simulator communication will start when the simulator has been launched.
During communication, [Communication] → [Start] is checked, and the [Communication] icon is depressed.
![]() |
or | ![]() |
Double-click on a cell under [Value] to display the [Write Memory] dialog.
It is also possible to write values or to bit-write by clicking the ON/OFF icon.
|
When connecting MONITOUCH to a PLC after operations are verified, configure as below.
|
When communication is not successful:
If the simulator's communication settings are not correct, the V/TS series cannot communicate with a PC properly.
If not successful, click [Communication] → [End] on the simulator to abort communication. Be sure to select [File] → [Communication Setting] and check the settings.
<Serial communication>
Select [File] on the simulator, check that [Comm. through USB] and [Comm. through Ethernet] are not checked, and click [Communication Setting].

Set the COM number for [Communication Port]. Set the same COM number as that on the PC.
<USB communication>
Select [File] on the simulator and check [Comm. through USB].
<Ethernet communication>


