The data displayed in a trend graph is different from the most recent data in the PLC.
The trend graph is not redrawn.
The graph data once displayed is not updated unless the redraw command is specified.
To update to the newest data, turn bit 14 or 15 of the control device memory from OFF to ON (leading edge).