The screen is not switched according to the command from the PLC (external).
Check the value specified in read area "n + 2".
The value must be specified in the data format (DEC/BCD) as set in the screen data.
The set data format can be viewed in the following location.
* For details about how to check Read area, click here.
V8/TS series
Setting location: V-SFT-6 editor [System Setting] → [Hardware Setting] → [PLCx Properties] → [Communication Setting] → [Code]
V7 series
Setting location: V-SFT-5 editor [System Setting] → [PLC Communication] → [Communication Parameter] → [Detail] → [Code]
Example: Read area "n + 2" (D2)
Step a: Change to screen No. 5 according to read area "n + 2"
Step b: Change to screen No. 2 with an internal switch
Step c: Change to the same screen number as step a (screen No. 5) according to read area "n + 2"
In this case, however, the same value is stored in read area "n + 2" so the command is not valid.
In such a case, it is possible to forcibly switch the screen to the screen number contained in read area "n + 2" at the leading edge [0 → 1] of bit 14 of read area "n + 1" (D1).