How to check the operation of screens without connecting to a PLC

Connection between PC and MONITOUCH
[Transferring screen data]
Click [File] -> [Transfer] -> [Download] on the V-SFT editor to display the [Transfer] dialog.

[Settings on the V10/V9 series]
After transferring data, switch to Local mode and display the Simulator Setting screen.
Configure settings on the Simulator Setting screen.
The model names of the logical ports (PLC1 - PLC8) are displayed each with a [Not Use (Actual Machine)]/[Use] selector switch for the simulator.
Select [Use] for devices to operate using the simulator and press [Apply].
For connection via Ethernet (when [Comm. Mode] is set to [Ethernet (UDP)]), also set the IP address of the PC.
Example: For USB connection

Example: For connection via Ethernet, also set the IP address of the PC.

[Starting the simulator]
Click [Transfer] -> [Simulator] on the V-SFT editor.
The simulator starts up.

The simulator starts communicating as soon as the [Simulator] window opens.
During communication, [Communication] [Start] is checked, and the [Communication] icon is depressed.

Double-click

It is also possible to bit-write by clicking the ON/OFF icons in the [Simulator] window.
|
When connecting MONITOUCH to a PLC after operations are verified, configure as below. |
When communication is not successful:
If the simulator's communication settings are not correct, the V series cannot communicate with a PC properly.
If not successful, click [Communication] [End] on the simulator to abort communication. Be sure to select [File] [Communication Setting] and check the settings.
<USB communication>
Select [File] on the simulator and check [Comm. through USB].
<Ethernet communication>

<Serial communication>
