When the MICREX-SX PLC is connected via the SX bus, the V10/V9 series unit encounters a communication error ("Time-Out") at startup.

  • Font Size
  • S
  • M
  • L
  • GLOBAL > HMI > V10/V9 series > Error > When the MICREX-SX PLC is connected via the SX bus, the V10/V9 series unit encounters a communication error ("Time-Out") at startup.
  • No : 4564
  • Displayed Date : 2025/12/01 13:46
  • Print

When the MICREX-SX PLC is connected via the SX bus, the V10/V9 series unit encounters a communication error ("Time-Out") at startup.

When the MICREX-SX PLC is connected via the SX bus, the V10/V9 series unit encounters a communication error ("Time-Out") at startup.

Category : 

Answer

Check the [Waiting time for structure check] and [Fail-soft operation setting] settings on the SX side.

  • If the [Waiting time for structure check] setting is too short, an error (serious fault) may occur in the configuration check because the V10/V9 series unit will not start up in time.
  • Configuring a fail-soft startup setting will prevent a serious fault from occurring even if the V10/V9 series unit does not start up in time for the configuration check and thereby prevent a communication error.

 

 

 

The setting procedure is described using the "SX-Programmer Expert (D300Win)" SX tool software as an example. The setting procedure is the same for "SX-Programmer Standard".

 

Waiting time for configuration check

  1. Click [System properties] in the system definition window and then click the [Properties] button.


     
  2. Set [Waiting time for structure check] on the [System Running Definition] tab window as follows.

    V10: 20 (s)
    V9: 30 (s)



     

Fail-soft operation setting

  1. Click the [Fail-soft operation setting] tab in the [System properties] window.
  2. Select [Partial Fail-soft start up] and a value for [Start Station No. of fail-soft running] in the [Fail-soft start up mode selection] area.

      * Set a value so that the SX station number of the V10/V9 series unit is included in the fail-soft startup.

        

* For more information on the configuration check wait time and fail-soft startup operation mode, refer to the SX manual.

* For information on how to use "SX-Programmer Expert (D300Win)" and "SX-Programmer Standard", refer to the corresponding manual.