When I compiled a project created in D300win, a warning message appeared saying 'The remainder capacity of the High speed PG memory has been decreasing...' What does this message mean?
    
      When I compiled a project created in D300win, a warning message appeared saying 'The remainder capacity of the High speed PG memory has been decreasing...' What does this message mean?
    
  
    - Category : 
 
    - 
      
    
 
  
 
    Answer
  
    The SPH3000 series has 'high-speed program (high-speed PG) memory' area in the program memory.
When you store a POU in this area, the POU execution speed becomes approximately three times faster.
The warning message means that the high-speed program memory space is low.
F.Y.I
If there is not enough high-speed PG memory to assign a POU, for example, by adding a circuit to the POU,
 the POU is assigned to the normal area.
Preferentially assign POUs that need to be processed at a high-speed to the high-speed PG memory, which is
 fixed to 224K bytes. Execute also the optimized compilation (compression of the execution codes) of the
 POUs assigned to the high-speed PG area, and re-assign the POUs of a low-priority task to the normal area.
* For more information on the specifications and usage of the high-speed PG memory, refer to the user’s 
manual 'SX-Programmer Expert (D300win) Reference (FEH257) version 'q' or later, '10-5 Optimized
 Compilation of POU (For SPH3000 series).'