The Card Format switch (SRAM format) is not effective when pressed.
<Causes> The set word count for [Memory Card Emulation Area] is too small. There is no memory card mode icon. <Solutions> Select [System ... Show Detail
Graphics do not move on an animated screen (in graphic or graphic relay mode).
The causes and solutions are explained for cases where the following parts are used. TS/V8 Graphic V7 Series Graphic Relay Graphic <Causes> Pa... Show Detail
Transparency of a pattern is not effective on an animated screen.
<Cause> The size of the pattern is greater than 4,088 dots. <Solution> The transparency setting is enabled for pattern sizes up to 4,088 dot... Show Detail
In the alarm tracking display, alarm data is not tracked for the specified number of times.
<Cause> [Buffering Area Setting] → [Number of Data to Save] is small. <Solution> Increase the number set for [Number of Data to Save]. For ... Show Detail
When a character entry switch is pressed, the switch name on it disappears.
<Cause> The character entry key switch is set as [Draw Mode: REP]. <Solution> Set [Draw Mode: XOR]. When using characters from the graphic ... Show Detail
Messages are not displayed in the alarm tracking display.
<Causes> [Start Bit] for sampling control device memory is checked, but the bit is not ON. The reset bit for sampling control device memory is ON. T... Show Detail
Communication between the PLC and the V/TS series is slow.
To speed up communications, try the following method. [When creating screens] When creating screens, consider the following points to improve the communi... Show Detail
I cannot make entries with a keypad.
<Causes> There is no entry mode icon (no cursor is displayed). The keypad ID number is different from the entry mode ID number (all keys in the keypa... Show Detail
Vertical lines are drawn in the trend sampling area but disappear.
<Cause> A drawing item (line) is placed in the trend sampling area. Drawing items must not be placed over the area. <Solution> TS/V8 ... Show Detail
The PLC memory address for a part is garbled as "??" or is "blank".
<Causes> When the PLC model setting is changed, it is replaced with device "??". PLC2 - 8 (Temperature Control/PLC2Way with the V7 series) are set as... Show Detail
1-10 of Total 30