Previous numeric data or characters remain in a numerical data display or character display part.
<Causes> TS/V8/V7 series The number of parts with the [Transparent] or [Shadow] setting has exceeded the number available on one screen. V6 series... Show Detail
Negative values or decimal fractions cannot be entered with a keypad.
[Negative values cannot be entered] <Causes> Wrong operation of the keypad. The display type of entry target is set as "no sign". <Solutions... Show Detail
Trend graphs cannot be displayed.
<Causes> No data is stored in the device memory address for each graph number. The number of points to display is not specified in the control device... Show Detail
Graphics do not move on an animated screen (in graphic or graphic relay mode).
The causes and solutions are explained for cases where the following parts are used. TS/V8 Graphic V7 Series Graphic Relay Graphic <Causes> Pa... Show Detail
Transparency of a pattern is not effective on an animated screen.
<Cause> The size of the pattern is greater than 4,088 dots. <Solution> The transparency setting is enabled for pattern sizes up to 4,088 dot... Show Detail
Vertical lines are drawn in the trend sampling area but disappear.
<Cause> A drawing item (line) is placed in the trend sampling area. Drawing items must not be placed over the area. <Solution> TS/V8 ... Show Detail
The Card Format switch (SRAM format) is not effective when pressed.
<Causes> The set word count for [Memory Card Emulation Area] is too small. There is no memory card mode icon. <Solutions> Select [System ... Show Detail
The POWER LED does not light up or flashes.
[The LED does not light up] <Causes> Power to the V/TS2060 series is not supplied properly. The LED is faulty (normal screen display). MONITOUCH is... Show Detail
MONITOUCH does not switch from the RUN screen to the Main Menu screen.
Press the [SYSTEM] switch, and when the switch menu is displayed press the [F1] (MODE) switch. [If the switch menu is not displayed when the [SYSTEM] sw... Show Detail
The screen is not switched according to the command from the PLC (external).
The causes are listed below. <Causes> The screen number to display is not specified in read area "n + 2". The specified screen number is the same as... Show Detail