When a character entry switch is pressed, the switch name on it disappears.
<Cause> The character entry key switch is set as [Draw Mode: REP]. <Solution> Set [Draw Mode: XOR]. When using characters from the graphic ... Show Detail
In the alarm tracking display, alarm data is not tracked for the specified number of times.
<Cause> [Buffering Area Setting] → [Number of Data to Save] is small. <Solution> Increase the number set for [Number of Data to Save]. For ... Show Detail
The lamp lights up even though the bit in the lamp device memory is not ON.
<Cause> The lamp device memory is used redundantly. <Solution> Check if the same address as the lamp device memory is used in the screen dat... Show Detail
Pressing the reset switch does not clear history data.
<Causes> The switch is not pressed twice. The switch function is not set to [Reset]. The switch is disabled according to the interlock setting. ... Show Detail
A screen in multiple languages is created; however, the displayed language does not change.
<Causes> A wrong language number is specified for the switch [Function: Language changeover]. (V8/TS series only) The screen is not refreshed after t... Show Detail
The PLC memory address for a part is garbled as "??" or is "blank".
<Causes> When the PLC model setting is changed, it is replaced with device "??". PLC2 - 8 (Temperature Control/PLC2Way with the V7 series) are set as... Show Detail
Transparency of a pattern is not effective on an animated screen.
<Cause> The size of the pattern is greater than 4,088 dots. <Solution> The transparency setting is enabled for pattern sizes up to 4,088 dot... Show Detail
Messages are not displayed in the alarm tracking display.
<Causes> [Start Bit] for sampling control device memory is checked, but the bit is not ON. The reset bit for sampling control device memory is ON. T... Show Detail
Communication between the PLC and the V/TS series is slow.
To speed up communications, try the following method. [When creating screens] When creating screens, consider the following points to improve the communi... Show Detail
Previous numeric data or characters remain in a numerical data display or character display part.
<Causes> TS/V8/V7 series The number of parts with the [Transparent] or [Shadow] setting has exceeded the number available on one screen. V6 series... Show Detail