  • "Touch Switch is Active"

    <Cause> This error is displayed when the power is turned on while a touch switch is being pressed. <Solutions> Remove your finger from the s... Show Detail

    • No:4713
    • Displayed Date:2025/12/01 13:50
  • "Receive timeout"

    This error may be displayed on the configuration software V-SFT when data is transferred. Possible causes and solutions are given below. [When the transf... Show Detail

    • No:4877
    • Displayed Date:2025/12/01 13:49
  • "Communication Error Received Code No. 05"

    [Communication with a PLC] Refer to the following FAQ page. "No:4708 Communication error "Error code received" [Communication with simulator] This err... Show Detail

    • No:4715
    • Displayed Date:2025/12/01 13:50
  • "Insert Storage in TS" "Insert CF Card in xx" (xx:V8 or V7)

    Though automatic program uploading upon power-on is enabled by screen configuration, no storage device(SD card, USB memory, CF card, etc.) is inserted in the... Show Detail

    • No:4714
    • Displayed Date:2025/12/01 13:49
  • "The font file cannot be found."

    This error is displayed when Gothic fonts used in the screen data are not installed. <Solutions> Update the V-SFT editor to version 5 from our webs... Show Detail

    • No:4720
    • Displayed Date:2025/12/01 13:49
  • "SIM Communication Error Simulator Not Connected", "Communication error Check I/F driver"

    This error is displayed at the top left corner on the V/TS series when simulator communication is not established correctly between the V/TS series and the P... Show Detail

    • No:4711
    • Displayed Date:2025/12/01 13:50
  • "Editor is occupied by another port"

    This error may be displayed on the configuration software V-SFT when data is transferred via Ethernet. Possible causes and solutions are given below. &... Show Detail

    • No:4722
    • Displayed Date:2025/12/01 13:50
  • "Screen No. Error"

    At the start of communication, the V8/TS series initially displays the screen corresponding to the value specified for "n+2" in [Read Area]. "Screen No. Err... Show Detail

    • No:4710
    • Displayed Date:2025/12/01 13:50
  • "The check level is wrong."

    <Cause> The screen data you attempted to open includes a function not supported by the V-SFT version in use. <Solution> Update the V-SFT ver... Show Detail

    • No:4721
    • Displayed Date:2025/12/01 13:50
  • "The size is too large to communicate."

    This error may be displayed on the configuration software V-SFT when data is transferred. Possible causes and solutions are given below. <Causes> ... Show Detail

    • No:4719
    • Displayed Date:2025/12/01 13:50