How to connect to a temperature controller / inverter without connecting to a PLC
The method differs according to the TS/the V series model. TS/V8 series Select [System Setting]→[Hardware Setting]→[PLC1] on the V-SFT editor and configure... Show Detail
How to read or write data between the PLC, temperature controller and inverter at regular intervals
Use [Device Memory Map Setting] . Periodic Reading Click [System Setting]→[Device Memory Map] → [PLCn].Select a device memory map number and click [OK]. ... Show Detail
Ladder transfer cannot be performed properly.
The solution varies depending on the connection method between the PC and the V8/TS series. There are three connection methods: USB, Ethernet, serial (V-CP ... Show Detail
How to limit the values that can be entered through the keypad
Follow the steps below. Click on the numerical data display part (Function: Entry Target). Display the [Num. Display] dialog, select [Operation/Alarm] and c... Show Detail
The PLC memory address for a part is garbled as "??" or is "blank".
<Causes> When the PLC model setting is changed, it is replaced with device "??". PLC2 - 8 (Temperature Control/PLC2Way with the V7 series) are set as... Show Detail
How to give headings to CSV files output by sampling
Create a CSV file of headings and store it on the CF card beforehand. The headings can be added to CSV files. Example: Buffering area No. 2, Filename...SMP0... Show Detail
Vertical lines are drawn in the trend sampling area but disappear.
<Cause> A drawing item (line) is placed in the trend sampling area. Drawing items must not be placed over the area. <Solution> TS/V8 ... Show Detail
Messages are not displayed in the alarm tracking display.
<Causes> [Start Bit] for sampling control device memory is checked, but the bit is not ON. The reset bit for sampling control device memory is ON. T... Show Detail
Characters are not displayed in character display parts as intended.
The action to take varies depending on the symptom. [No text is displayed or a part of text is not displayed] <Causes> Windows fonts are used but ... Show Detail
Previous numeric data or characters remain in a numerical data display or character display part.
<Causes> TS/V8/V7 series The number of parts with the [Transparent] or [Shadow] setting has exceeded the number available on one screen. V6 series... Show Detail