The screen is not switched according to the command from the PLC (external).
The causes are listed below. <Causes> The screen number to display is not specified in read area "n + 2". The specified screen number is the same as... Show Detail
Three methods are available for editing. [Method 1: Select the overlap part] Select the overlap part. The overlap part is enclosed with handles. S... Show Detail
At the start of communication, the V8/TS series initially displays the screen corresponding to the value specified for "n+2" in [Read Area]. "Screen No. Err... Show Detail
This error is displayed on the TS/V series. Nothing can be displayed because font data for screen display is not found. Font data transfer was canceled dur... Show Detail
MONITOUCH does not recognize the storage dvice.
<Causes> The file system of the storage device is not supported. The CF card cover is open (V8 series only). The error status is set in $s497 (or $s... Show Detail
How to use a storage device with minimal concern for its life or other limitations
The number of the storage device write times can be reduced as described below. [TS/V8] Increase the number of sampling times from the primary storage targ... Show Detail
How to connect two temperature controllers/inverters from different manufacturers
Two methods are available. [Method 1: When each controller is included in the options in the [Device Connection Setting] dialog] (V8/TS only) The V8/TS can... Show Detail
Communication between the temperature controller and the V series is slow (V7 series).
To speed up communications, try the following method. The condition can also be improved as described below. <Baud rate> Increase the communicatio... Show Detail
Characters are not displayed in character display parts as intended.
The action to take varies depending on the symptom. [No text is displayed or a part of text is not displayed] <Causes> Windows fonts are used but ... Show Detail
Negative values or decimal fractions cannot be entered with a keypad.
[Negative values cannot be entered] <Causes> Wrong operation of the keypad. The display type of entry target is set as "no sign". <Solutions... Show Detail