The POWER LED does not light up or flashes.
[The LED does not light up] <Causes> Power to the V/TS2060 series is not supplied properly. The LED is faulty (normal screen display). MONITOUCH is... Show Detail
MONITOUCH does not switch from the RUN screen to the Main Menu screen.
Press the [SYSTEM] switch, and when the switch menu is displayed press the [F1] (MODE) switch. [If the switch menu is not displayed when the [SYSTEM] sw... Show Detail
The screen is not switched according to the command from the PLC (external).
The causes are listed below. <Causes> The screen number to display is not specified in read area "n + 2". The specified screen number is the same as... Show Detail
Pressing a switch does not activate anything.
<Causes> Interlock is set for the switch. ON delay is set for the switch. (TS/V8 only) Touch switch position is deviated. When the screen change sw... Show Detail
The lamp lights up even though the bit in the lamp device memory is not ON.
<Cause> The lamp device memory is used redundantly. <Solution> Check if the same address as the lamp device memory is used in the screen dat... Show Detail
I cannot make entries with a keypad.
<Causes> There is no entry mode icon (no cursor is displayed). The keypad ID number is different from the entry mode ID number (all keys in the keypa... Show Detail
When a character entry switch is pressed, the switch name on it disappears.
<Cause> The character entry key switch is set as [Draw Mode: REP]. <Solution> Set [Draw Mode: XOR]. When using characters from the graphic ... Show Detail
The data displayed in a trend graph is different from the most recent data in the PLC.
<Cause> The trend graph is not redrawn. <Solution> The graph data once displayed is not updated unless the redraw command is specified. To ... Show Detail
Pressing the reset switch does not clear history data.
<Causes> The switch is not pressed twice. The switch function is not set to [Reset]. The switch is disabled according to the interlock setting. ... Show Detail
How to display overlap parts from the PLC (external)
There are four overlap part types. Normal overlap Call-overlap Multi overlap Global overlap In the case of external commands, the display method diffe... Show Detail