MONITOUCH does not switch from the RUN screen to the Main Menu screen.
Press the [SYSTEM] switch, and when the switch menu is displayed press the [F1] (MODE) switch. [If the switch menu is not displayed when the [SYSTEM] sw... Show Detail
The data displayed in a trend graph is different from the most recent data in the PLC.
<Cause> The trend graph is not redrawn. <Solution> The graph data once displayed is not updated unless the redraw command is specified. To ... Show Detail
Transparency of a pattern is not effective on an animated screen.
<Cause> The size of the pattern is greater than 4,088 dots. <Solution> The transparency setting is enabled for pattern sizes up to 4,088 dot... Show Detail
How to copy a screen from one file to another
Three methods are available. Follow the steps below. [Method 1: Copy each item] Select [File] → [Comparing]. Enter filenames for [Comparison] (source) and... Show Detail
Set a value other than "0" for system memory $s77 (overlap exclusive function). Any switches other than those (including the overlap system button) on the o... Show Detail
How to display screens in foreign languages
The following languages are available with the V / TS. Supported Language List To create screens in the above languages, the following software and har... Show Detail
How to assign a function to each function switch
The function switches can be used for preset purposes in the RUN mode. [Function switch operation regardless of the currently displayed screen] Select [S... Show Detail
How to copy a TS/V8 screen program to V7 or earlier models
The TS/V8 screen program cannot be copied to V7 or earlier models. Copying of screens and parts such as switches also cannot be performed. Please recreated... Show Detail
Communication between the PLC and the V/TS series is slow.
To speed up communications, try the following method. [When creating screens] When creating screens, consider the following points to improve the communi... Show Detail
The screen is not switched according to the command from the PLC (external).
The causes are listed below. <Causes> The screen number to display is not specified in read area "n + 2". The specified screen number is the same as... Show Detail