I want to show a multi-overlap using PLC command but the overlap does not appear.
Check the following points: Multi-overlap (icon) is not place on the screen. Multi-overlap setting (icon) is not correct. Macro commands are not corr... Show Detail
The graph of a trend part (Display Mode: Real Time Display) is not displayed.
<Causes> No data is stored in the device memory address for each graph number. The number of points to plot is not specified in the control device me... Show Detail
Cannot make entries with a keypad.
There is no entry target (no cursor is displayed). Entered valued is out of preset alarm lange. (the ENT key is not valid) The bit (Bit 15) for enabling/di... Show Detail
Pressing the reset switch does not clear history data.
<Causes> The switch is not pressed twice. The switch is disabled according to the interlock setting. <Solutions> Press the "Reset" switch... Show Detail
Pressing a switch does not activate anything.
<Causes> Interlock is set for the switch. Touch switch position is not aligned. When using a switch for changing screens (Function: Screen Change-ov... Show Detail
Use "Text comparison". If a file agrees with another one using text comparison, they are the same screen program. Text comaprison is available to check t... Show Detail
The lamp lights up even though the bit in the lamp device memory is not ON (OFF).
<Cause> The lamp device memory is used redundantly. <Solution> Check if the same address as the lamp device memory is used in the screen data ... Show Detail
Negative values or decimal fractions cannot be entered with a keypad.
[Negative values cannot be entered] <Causes> Wrong operation of the keypad. The display type of entry target is set as "no sign". <Solutions... Show Detail