"It is not possible to open this file because there is a function that is not able to use."
<Causes> The screen data you attempted to open includes a function not supported by the V-SFT version in use. <Solutions> Update the V-SFT v... Show Detail
Number of the characters in a variable comment exceeds 255 in the D300Win(Ver.3) programming software. Delete the comment. D300Win(Ver.3) is designed to hav... Show Detail
"The size is too large to communicate."
This error may be displayed on the configuration software V-SFT when data is transferred. Possible causes and solutions are given below. <Cause> T... Show Detail
The PLC device memory address for a part is garbled as "??" or is "blank".
<Causes> When the PLC model setting is changed, it is replaced with device "??". PLC2 - 8 are set as "not used" (delete). Variable name cooperation ... Show Detail
I cannot set the IP address to setup VPN connection.
Check the settings below: V10/V9's calendar settings If date and time set on the V10/V9 unit is not correct, it is not possible to establish VPN connecti... Show Detail
When Fuji Electric MICREX-SX is selected, this error is displayed if screen data uses input/output memory (X, Y), or P link/PE link/FL-net (CPU No. 8, 9) mem... Show Detail
"Editor is occupied by another port"
This error may be displayed on the configuration software V-SFT when data is transferred via Ethernet. Possible causes and solutions are given below. &... Show Detail
An unavailable device memory address is set or the available device memory range is exceeded. Causes The causes are listed below. Device memory set in t... Show Detail
This error is displayed in Local mode when a battery problem has occurred to the V series. (The battery is set in the V series at shipment.) <Cause>... Show Detail
This error may be displayed on the configuration software when data is transferred. When the V series does not respond within the set time, this error occurs... Show Detail