I want to create a flow chart screen but it is too large to fit in single screen.
Images can be laid out four times the screen size in height or width. The whole are of a large image can be confirmed easily by scrolling the screen. As you... Show Detail
How to change the start-up screen (splash screen)
It is possible to change the screen to be displayed while the V10/V9 series unit is starting up. The default splash screen V10 V9 ... Show Detail
I want to show a multi-overlap using PLC command but the overlap does not appear.
Check the following points: Multi-overlap (icon) is not place on the screen. Multi-overlap setting (icon) is not correct. Macro commands are not corr... Show Detail
I cannot set the IP address to setup VPN connection.
Check the settings below: V10/V9's calendar settings If date and time set on the V10/V9 unit is not correct, it is not possible to establish VPN connecti... Show Detail
The PLC device memory address for a part is garbled as "??" or is "blank".
<Causes> When the PLC model setting is changed, it is replaced with device "??". PLC2 - 8 are set as "not used" (delete). Variable name cooperation ... Show Detail
"The size is too large to communicate."
This error may be displayed on the configuration software V-SFT when data is transferred. Possible causes and solutions are given below. <Cause> T... Show Detail
What standards is V10/V9 series compliant with?
Refer to the following for the supported standards of the V10/V9 series. <V10 series> CE, UKCA, KC, UL, ANSI/ISA, EAC and Radio Act ・・・ click here ... Show Detail
Messages are not displayed in the alarm tracking display.
<Causes> The bit corresponding to the message is not ON. The display mode for displaying messages is not checked in the [Alarm Device] settings of th... Show Detail
The graph of a trend part (Display Mode: Real Time Display) is not displayed.
<Causes> No data is stored in the device memory address for each graph number. The number of points to plot is not specified in the control device me... Show Detail
The lamp lights up even though the bit in the lamp device memory is not ON (OFF).
<Cause> The lamp device memory is used redundantly. <Solution> Check if the same address as the lamp device memory is used in the screen data ... Show Detail