When I set offset on the analog module (NP1AXH8I-MR) by using software (parameters) and disable the software offset setting by operating hardware (rotary switch), the software offset still work. Why?

  • Font Size
  • S
  • M
  • L
  • GLOBAL > PLC > SPH > I/O > When I set offset on the analog module (NP1AXH8I-MR) by using software (parameters) and disable the software offset setting by operating hardware (...
  • No : 1667
  • Displayed Date : 2023/04/25 19:00
  • Print

When I set offset on the analog module (NP1AXH8I-MR) by using software (parameters) and disable the software offset setting by operating hardware (rotary switch), the software offset still work. Why?

When I set offset on the analog module (NP1AXH8I-MR) by using software (parameters) and disable the software offset setting by operating hardware (rotary switch), the software offset still work. Why?
Category : 

Answer

After changing the range with the rotary switch, turn off the power once and then turn it on again, and the software offset setting will be disabled.