I will use the analog current input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
I will use the analog current input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
- Category :
-
Answer
No, you can't.
The relationship between i, which is the sensor output current, and i1 and i2, which are the CH input currents of the PLC, is expressed as i = i1 + i2. The values of i1 and i2 are not the same due to the variation between parts so that it is impossible to input a proper value.