An address error occurs when I read a battery error of the standby CPU (CPU1) from the operating CPU (CPU0).

  • Font Size
  • S
  • M
  • L
  • GLOBAL > PLC > SPH > Application > An address error occurs when I read a battery error of the standby CPU (CPU1) from the operating CPU (CPU0).
  • No : 1572
  • Displayed Date : 2023/04/25 19:00
  • Print

An address error occurs when I read a battery error of the standby CPU (CPU1) from the operating CPU (CPU0).

An address error occurs when I read a battery error of the standby CPU (CPU1) from the operating CPU (CPU0).
Category : 

Answer

In a redundant system, both CPUs are identified as CPU0 and you cannot read a battery error of the standby CPU. Determine the condition of the standby CPU from the resource operation/running information and configuration/fault information.