I use the hot plug base board with station No. Setup Function (Type_NP1BS-13D). When a module is removed, a nonfatal fault occurs. Please tell me how to distinguish it from other nonfatal faults

I use the hot plug base board with station No. Setup Function (Type_NP1BS-13D). When a module is removed, a nonfatal fault occurs. Please tell me how to distinguish it from other nonfatal faults
Category : 

Answer

Check the following system memory.
If %MX10.4.5 (SM45) 'I/O module error' is turned on, removal of a module may be the cause of the nonfatal fault.
[Related document]
For the details of the system memory, refer to either of the following manuals depending on your loader.
When using Expert, see '1-2 Memory Specifications' in the user's manual 'Instructions' (FEH200).
When using StandardV3, see '2-2-2 Description of memories' in the user's manual 'Instructions' (FEH588).