Are there any restrictions on the mounting position of the I/O modules and communication modules on the base? I'd like to place the communication module on the right-end of the base board.

  • Font Size
  • S
  • M
  • L
  • GLOBAL > PLC > SPH > Others > Are there any restrictions on the mounting position of the I/O modules and communication modules on the base? I'd like to place the communication m...
  • No : 1673
  • Displayed Date : 2023/04/25 19:00
  • Print

Are there any restrictions on the mounting position of the I/O modules and communication modules on the base? I'd like to place the communication module on the right-end of the base board.

Are there any restrictions on the mounting position of the I/O modules and communication modules on the base? I'd like to place the communication module on the right-end of the base board.
Category : 

Answer

Modules that use the processor bus, such as the P/PE link and FL-net modules, need be mounted on the slot equipped with the processor bus.
Other communication modules (general-purpose communication, Ethernet, T-link, etc.) can be mounted on any slots of the CPU base and expansion base as long as they are on the SX bus.