The product type without 'RI' judges ON/OFF of the inputs by current. On the other hand, the product type with 'RI' judges ON/OFF of the inputs by voltage. ... Show Detail
In a redundant system, both CPUs are identified as CPU0 and you cannot read a battery error of the standby CPU. Determine the condition of the standby CPU fr... Show Detail
The input/output data continue to be valid after the CPU is switched. (The previous values are retained.) Show Detail
How do I use a manual pulse generator with the positioning module (Type_NP1F-MP2/MA2)?
Set the I/O area of the positioning module following the steps below. 1) Set 'h1C00' in the offset word address +16 (Ch1 Set value area: Low word). (Set ... Show Detail
When the common memory system is used, this can be achieved by handshaking with an application using part of the link memory. Without handshaking, it is not... Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail
The MICREX-SX does not include a communication module having interfaces with Mitsubishi's original networks, MELSEC-NET/B or NET/10 or CC-LINK. Alternativel... Show Detail
I cannot download a project to the user ROM card inserted in the CPU. What is a possible cause?
This problem is probably caused by the following reasons: [For SPH300/2000/3000 series] 1) The CPU mode selection switch is not set at the 'UROM-TERM' pos... Show Detail
You can connect an SX series CPU to D300win via USB, Ethernet or a dedicated loader cable, depending on the model. Configure the communication settings acco... Show Detail
Check the following system memory. (1) Configuration information %MW10.52 to %MW10.67 (WSM52 to 67) (2) Configuration fault information %MW10.68 to %MW1... Show Detail